Emerson inverter repair fault code analysis
Shanghai Puyuan inverter maintenance experts around you, to help you solve all problems, professional no-chip maintenance of the drawings. Prior to the maintenance of Emerson series inverters, it is necessary to understand the fault codes, otherwise there is no way to start. I collect and sort out this information in order to share it with everyone and I hope to help everyone in the future.
Fault type
error code
Fault type
error code
Input phase loss
P0FF
Input undervoltage
E008
Output phase loss
E001
Accelerating overcurrent
E009
Module protection
E002
Slow down
E010
Overheated inverter
E003
Constant speed overcurrent
E011
Rectifier overheat
E004
Acceleration over pressure
E012
Read and write failures
E005
Deceleration over pressure
E016
Contactor not sucked
E006
Constant speed overpressure
E018
Current detection circuit failure
E007
Control power supply overvoltage
E019
Current detection circuit failure
E007
Control power supply overvoltage
E019
1, current detection failure (such as reported E019, E001):
(1) The control board Q1 (15050026) is bad.
(2) 7840 bad: When the inverter is powered on, use the DC file, connect the black to the 5 pin, red to the 6, 7, and 8 pins respectively. The values ​​are 2.5, 2.5, and 5 are normal, otherwise the 7840 is bad.
(3) Small board bad: When the inverter is powered on, use the DC gear, connect the 5 pin of the 7840 to black, and the red pin to the small board should be 2.5, 2.5, 2.5, 3.4 1.5, 0, 1.6 from left to right respectively.
If the value is incorrect, the small board is bad: At this time, three small ICs (39030024 LMV393) in the bad one can be replaced. If not, replace the small board.
2, Emerson inverter repair display POFF:
Drive plate POFF, the normal CVD voltage should be 2.6-2.7, if measured 1.9, may R51, R52, C36, C37, one of the bad cable, which Electrolytic capacitor is the worst. POFF is only reported when the belt motor is running, and the driver board transformer may also be damaged.
3, bad buffer resistance:
Buffer resistance and filter bulk capacitance are paired. If one is bad, the other is probably bad. The bad buffer resistance may also be caused by the relay not picking up (the relay is bad or the control board is bad, or the components on the circuit connected to both are bad). For single-phase input (220V) frequency converters, special attention should be paid: if there is no display or fry, it is likely that the user is connected to three-phase power (380V). (The fault record of the control board can be checked: whether the bus voltage is controlled by 310 Changed to 540). At this point, the rectifying bridge of IPM is already broken, and the large capacitor of the filter is also bad (or burst or the top surface is hardened). If you only power up after replacing the IPM, you will hear a "buzzing, buzzing" sound (the sound in the capacitor). You should immediately switch off the power, otherwise the rectifier bridge of the IPM will be damaged. Found a big bad capacitor, it is best to replace it with a new one. Because the capacitor is easy to damage and aging devices.
4, Emerson inverter repair display instability:
The first display, then no, the fan stopped, the voltage is only 12, this phenomenon is generally bad U1 thick film. Reported fault E015: power-on indicator light, keyboard does not shine, just like a fan - fan short-circuit
5, no brake:
The brake pipe of 01180099, 01180100, 01180113, 01180114 is not in the IPM. The explosion and non-display of the inverter may be caused when the inverter is stopped and braked. Therefore, after the IPM is replaced, the brake circuit must be checked for good or bad: Braking optocoupler, brake tube (MOS tube is not measured, can measure its series freewheeling diode, the normal should be about 0.37), the gate resistance (that is, the gate resistance of the MOS tube, the normal should be 100 ohms) . After repairing the power supply, the TD900 F093 is changed to 150, reported to E007, red is connected to P(+), and black is connected to PB. If the voltage is beating at 17-30, the brake is normal. TD3200 F133=150 DC voltage 270-350V Brake is active.
6, Emerson inverter repair fried rectifier bridge:
If the measured partial rectifier bridge is damaged and the inverter bridge is good, it may be caused by the ignition between the positive and negative busbars. Moisture is the main cause, generally there is a drop of water between the positive and negative terminals, or there is a drop of water that causes a blower between the positive terminal and the radiator. The insulation of the terminal of such a bad machine has deteriorated and must be replaced, otherwise it will be blown up after being powered on. Another reason is that the large capacitor of the filter is short-circuited (or burst or the top surface is hardened), and the capacitor must be replaced.
7, the machine hits:
That is, when the fan is fast, there is no display. Generally, the control board is short-circuited, the control board is removed and the power is turned on again. If it is still hiccup, it may be that the thick film surrounding the device is broken. For example, the resistance value of the TD1000 large-size R56 resistor 27 Euro becomes much larger, that is, the hiccup protection circuit itself. broken. Switching power supply does not work, can measure the voltage of one of the resistors, such as a bit voltage and jump, indicating that the switching power supply has started, but the back of the circuit is short-circuited (connected tin between the transformer's feet, the filter capacitor touches), the hiccup protection circuit is kick in. If there is no voltage, it means that the switching power supply does not start to oscillate. It is generally a bad thick film or bad 2844 and nearby devices.
8, Emerson inverter maintenance fan powerless, slow speed:
D6 breakdown of the EV1000. Telegram 8888: FECDF21U1 board U8 bad, with small cracks. EV1000 such as 01180128, with load shutdown report 8888: Transformer inductance worse or PC9 original secondary insulation is not enough.
9, press operation 8888: drive optocoupler short circuit.
10, EV1000 large volume: the original fault is the bomber, repaired after the operation without output or E019, often bad is U9. No output Sometimes Q2 is also bad.
Maintenance hotline
Rectifier bridge is to seal the rectifier tube in a shell. Points full bridge and half bridge. The full bridge connects the four diodes of the connected bridge rectifier circuit together. The half bridge is half of four diode bridge rectifiers, and two half bridges can be used to form a bridge rectifier circuit. One half bridge can also be used to form a full-wave rectifier circuit with a center-tapped transformer. Select a rectifier bridge to consider. Rectifier circuit and operating voltage.